Testing Procedures for Power Engineering

557 bytes added, 12:46, 23 April 2014
13.4.2.1 Electrical Life
The electrical life of contactors, motor switches, and auxiliary current switches used in power engineering is classified into use categories which are shown in <xr id="tab:Important Use Categories and Their Typical Applications for Contactors and Power Switches"/> (Tab. 13.1).
The making and breaking currents for tests IEC/EN 60947-4-1 are shown in Table 13.2 for the different use categories.
The electrical life of a motor switch is influenced primarily by arc erosion which is generated during make and break arcs on the contact surface. During AC-3 testing, for which the make current is six time the nominal rated current, the arc erosion is mainly caused by the make arcs, especially if frequent contact bounces > 2 ms occur. Therefore the bounce characteristic of switching devices primarily used for “normal” use in switching on and off electrical motors is of critical importance. If make and break currents are the same, as in the ultilisation categories AC-1 and AC-4, the break erosion dominates the arc erosion so much that make erosion can be neglected.
electrical life of auxiliary switches is of lesser importance since these devices see only smaller loads. Under certain conditions however requirements for make and beak capacity can be as high as 10 times the nominal current. This results in very severe requirements on the dielectric strength and recovery voltage of the arc affected region immediately after arcing.
<figtable id="tab:Verification of Electrical Life Conditions for Make and Break Tests of Contactors and Motor Starters by Utilization Category">'''Table 13.2: Verification of Electrical LifeConditions for Make and Break Tests of Contactorsand Motor Starters by Utilization Category''' {| class="twocolortable" style="text-align: left; font-size: 12px"|-!Ultilisation Category!Current!colspan="3" style="text-align:center"| Make operation!colspan="3" style="text-align:center"| Break Operation|-!!I<sub>e</sub>/A!I/I<sub>e</sub>!U/U<sub>e</sub>!cos n!I<sub>c</sub>/I<sub>e</sub>!U<sub>r</sub>/U<sub>e</sub>!cos n|-|AC-1|Alle Werte|1|1|0.95|1|1|0.95|-|}</figtable>
Fig. 13.2: