Contact Physics – Formulas

From Electrical Contacts
Revision as of 15:41, 7 January 2014 by Ermisch (talk | contribs) (Created page with "====6.4.2 Contact Physics – Formulas==== *'''Constriction resistance''' Re = D/2a (Single spot contact according to Holm; circular touching spot between clean contact surf...")

(diff) ← Older revision | Approved revision (diff) | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

6.4.2 Contact Physics – Formulas

  • Constriction resistance

Re = D/2a (Single spot contact according to Holm; circular touching spot between clean contact surfaces) Re = D/2Na (Multi-spot contact according to Holm without influence between the N individual spots) Re = D/2 x E ai + 3B D/32N² x E E (sij) i = j (Multi-spot contact according to Greenwood considering the influence between the spots)

als bild?


  • Contact resistance

RK = Re + Rf

  • Path resistance

Rd = Rb + RK

  • Contact resistance and contact force

R = 280D ³ E(F · r) K K (According to Holm model for film-free spherical contact surfaces with plastic deformation of the contact material; F < 1 N for typical contact materials) k RK = 9000 D H/ FK (According to Holm model for film-free spherical contact surfaces with plastic deformation of the contact material; F > 5 N for typical contact materials)


  • Dynamic contact separation (without considering magnetic fields caused by the current path)

FA 0,8 x I² (Rule of thumb with F in N and I in kA)

  • Contact voltage and max. contact temperature

T kmax 3200 UK

  • Contact resistance at higher contact forces (according to Babikow)

R = cF -m K K For F between 10 and 200 N K c = material dependent proportionality factor m = shape dependent exponent of the contact force

References

References